Omron SYSMAC C500-NC113 Operation Manual page 201

Position control units
Table of Contents

Advertisement

STOP During a Positioning Action with Completion Code 5 (Interrupt Feeding)
ORIGIN RETURN
Word m+1 bit 03
STOP (first time)
Word m+1, bit 15
Pulse output
Positioning Completed Flag
Word s+0, bit 00
Busy Flag
Word s+0, bit 07
No-origin Flag
Word s+0, bit 06
Execute Deceleration Stop
Word s+3, bit 15
Positioning action number
Word s+3, bits 10 to 00
Output code
Word s+2, bits 11 to 00
When STOP is executed for the first time during a positioning action with a
completion code of 5, positioning will be executed according to whatever data is
set for that positioning action (with interrupt feeding). When it is executed for a
second time (see the example diagram on the following page), positioning is in-
terrupted and decelerates to a stop.
1
0
1
0
1
0
1
0
1
0
Positioning is started and the
flag turns OFF after a delay
1
of approximately 10 ms.
0
Positioning cannot be restarted as long as the signal defined as the STOP com-
mand (either word m+1, bit 15, or an external interrupt signal) is ON, i.e., set to
"1."
Section
P
P+1
9-11
Time