Omron SYSMAC C500-NC113 Operation Manual page 189

Position control units
Table of Contents

Advertisement

9-10 Manual Operation
9-10-1 Data Settings
Initial Speed Number (X Axis: 2001; Y Axis: 6001)
HIGH-SPEED JOG Speed Number (X Axis: 2003; Y Axis: 6003)
LOW-SPEED JOG Speed Number (X Axis: 2004; Y Axis: 6004)
• When bit 12 is turned ON (↑), the EEPROM read/write designation (word
m+4/m+8, bit 13) is referenced and data is either read from or written to EE-
PROM.
• The setting of bit 13 determines whether data is to be written to EEPROM from
the internal RAM or read to internal RAM from EEPROM.
0: Write to EEPROM
1: Read from EEPROM
There are three manual feeding commands: HIGH-SPEED JOG, LOW-SPEED
JOG and INCH. Acceleration and deceleration are possible with HIGH-SPEED
JOG, but not with LOW-SPEED JOG. INCH operates one pulse at a time (from 1
to 100)). Although the following explanations are made with respect to the X-
axis, the explanations are the same for the Y-axis of the NC211.
15
Address
2001
• Set the initial speed number (bits 07 to 00) from 0 to 49.
• Speed addresses 4000 to 4049 (for the X axis) are referenced according to this
setting.
HIGH-SPEED JOG speed
Acceleration
Initial speed #0
15
Address
2003
• Set the HIGH-SPEED JOG speed number (bits 07 to 00) from 0 to 49.
• Speed addresses 4000 to 4049 are referenced according to this setting.
15
Address
2004
07
to
00
Initial
speed
number
Bits 07 to 00
HIGH-SPEED JOG speed
Acceleration
Initial speed number other than 0
07
to
00
HIGH-SPEED
JOG speed no.
Bits 07 to 00
07
to
00
LOW-SPEED
JOG speed no.
Bits 07 to 00
Section
9-10
Time