Braking distance (r52047, r52048)
This signal specifies the distance that the drive would travel if, e.g. it would be stopped using
an OFF1 command.
This braking distance is calculated under the assumption that at the ramp-function generator
input, a speed setpoint of 0 would be input and the speed actual value would go down to 0
with the set ramp-down time and the set rounding-off.
The braking distance calculation is only correct if, during braking, the ramp-down time and
the rounding-off do not change.
The braking distance is output in the same unit as the encoder position actual value r0482.
This means that one encoder revolution corresponds to a value of p400×2^p418
The braking distance is available in two different data formats:
● r52047 has the Unsigned32 data type
● r52048 has the FloatingPoint32 data type
10.9.2

Jog

See also function diagram 3125 in the SINAMICS DCM List Manual.
The JOG function can be applied via the binectors selected using p50435 index .00 to .07,
and via control word bit 8 and bit 9 (r898.8 & r898.9) (see function diagram for logic
operation).
The "Jog" function can only be executed if "Switch off" and "Operation enable" have been
applied.
The "Jog" function is applied by one or more of the sources referred to (binectors, control
word bits) entering the log. "1" state. During this, each source is assigned a setpoint (to be
selected using p50436).
If two or more sources apply the "Jog" function at the same time, then 0 is applied as the jog
setpoint.
For each source (binector, control word bit) with which the "Jog" function can be applied,
p50437 may be used to determine whether the ramp-function generator is bypassed
(binector r53170.11). In this case, the ramp-function generator operates with ramp-up time =
0 and ramp-down time = 0.
Procedure for applying jog:
If "Jog" is applied, the system is switched on and the jog setpoint applied via the ramp-
function generator. For this procedure, refer to the section titled "Switch on/Switch off
(ON/OFF1)".
Procedure for withdrawing jog:
Once the "Jog" function has been withdrawn, the procedure begins in the same way as the
"Switch off" function, as outlined in the section titled "Switch on/Switch off (ON/OFF1)". Once
n < nmin, the controller is disabled and, following a parameterizable time (p50085) of 0 to 60
s, the line contactor is opened (operating state o7.0 or higher). While the wait time that can
be parameterized using p50085 (max. 60.0 s.) is running, the drive remains in operating
state o1.3.
SINAMICS DCM DC Converter
Operating Instructions, 1.2012, C98130-A7066-A1-05-7619
Descriptions of functions
10.9 Setpoint channel
407