3.4.4.
Masking binary inputs, entering latching parameters and
definition of "double indications"
(see Section 5.5.5.)
The sub-menu 'Edit binary inputs' provides facility for excluding
(masking) binary signals from being recorded as events.
Every LED, signal and tripping command can be set to a latch or
not to latch via the sub-menu 'Edit signal outputs' or 'Edit trip
outputs', providing the 'LEDSigMode' parameter was also set to
latching beforehand.
Note that the green LED1 (standby signal) cannot be set to a
latching mode.
In the 'Edit binary inputs' menu, up to 30 pairs of consecutive
binary inputs can be combined to form double signals. A runtime
supervision can also be configured for each of them.
3.4.5.

Edit system parameters

(see Section 5.5.6.)
The settings made in the three sub-menus accessed via the 'Edit
system parameters' menu apply for all control and protection
functions. The three sub-menus are:
· Edit system I/O
· Edit system name
· Edit system password.