ABB REG316 4 Series Operating Instructions Manual page 320

Numerical generator protection
Table of Contents

Advertisement

ABB Switzerland Ltd
t Drop BuTrip
Reset delay for backup tripping attempt.
t Puls RemTrip
Transfer tripping impulse width.
t1 active
defines whether timer t1 is enabled or disabled.
'on'
Timer t1 enabled
'off'
Timer t1 disabled.
t2 active
defines whether timer t2 is enabled or disabled.
'on'
Timer t2 enabled
'off'
Timer t2 disabled.
RemTrip active
defines whether transfer tripping is enabled or disabled.
'on'
Transfer tripping enabled
'off'
Transfer tripping disabled.
EFP active
defines whether the end fault protection is enabled or disabled.
'on'
End fault protection enabled
'off'
End fault protection disabled.
Red active
defines whether the redundant logic is enabled or disabled.
'on'
Redundant tripping logic enabled
'off'
Redundant tripping logic disabled.
Start Ext active
defines whether the unconditional tripping logic is enabled or
disabled.
'on'
Unconditional tripping logic enabled
'off'
Unconditional tripping logic disabled.
RemTrip after
defines the delay for transfer tripping.
't1'
after BFP time t1
't2'
after BFP time t2.
NrOfPhases
defines the number of phases supervised.
'1'
single-phase operation
'3'
three-phase operation.
CurrentInp
defines the c.t. input channel. Single and three-phase c.t's
can be set. The first channel (R phase) of the group of three
selected must be specified for three-phase c.t's .
3-282
REG 316*4 1MRB520049-Uen / Rev. F