ABB REG316 4 Series Operating Instructions Manual page 298

Numerical generator protection
Table of Contents

Advertisement

ABB Switzerland Ltd
D. Pole slip settings - Pole-Slip
Summary of parameters:
Text
Unit
ParSet 4..1
Trip1
ZA
UN / IN
ZB
UN / IN
ZC
UN / IN
Phi
deg
WarnAngle
deg
TripAngle
deg
n1
n2
t-Reset
s
CurrentInp
AnalogAddr
VoltageInp
AnalogAddr
BlockGen
BinaryAddr
BlockMot
BinaryAddr
BlockInp
BinaryAddr
EnableZone1
BinaryAddr
Warning
SignalAddr
Generator
SignalAddr
Motor
SignalAddr
Zone1
SignalAddr
Zone2
SignalAddr
Trip1
SignalAddr
Trip2
SignalAddr
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active
3-260
REG 316*4 1MRB520049-Uen / Rev. F
Default
Min.
P1
(Select)
00000000
0,00
0,000
0,00
-5,000
0,00
0,000
090
60
000
0
090
0
1
0
1
0
5,000
0,500
0
0
F
F
F
F
ER
ER
ER
ER
ER
ER
ER
(see Section
5.11.).
Max.
Step
5,000
0,001
0,000
0,001
5,000
0,001
270
1
180
1
180
1
20
1
20
1
25,000
0,010