REG 316*4 1MRB520049-Uen / Rev. F
Block BFP
Input for blocking the function.
F:
not blocked
T:
blocked
xx:
all binary inputs (or outputs of protection functions).
Start L1, L2 or L3
BFP or RED Start in phase L1, L2 or L3
F:
disabled
T:
enabled
xx:
all binary inputs (or outputs of protection functions).
Start L1L2L3
BFP or RED Start in all three phases
F:
disabled
T:
enabled
xx:
all binary inputs (or outputs of protection functions).
External Start
starts the unconditional trip.
F:
disabled
T:
enabled
xx:
all binary inputs (or outputs of protection functions).
CB Off
signals that the circuit-breaker is fully open and also used to
start the end zone fault protection.
F:
CB not fully open
T:
CB fully open
xx:
all binary inputs (or outputs of protection functions).
CB On
signals that the circuit-breaker is fully closed.
F:
CB not fully closed
T:
CB fully closed
xx:
all binary inputs (or outputs of protection functions).