REG 316*4 1MRB520049-Uen / Rev. F
A further difference lies in the fact that the "a" factors only effect
the differential protection, whilst changing the reference values
of the A/D channels effects the currents for the entire protection
system (all functions and measured variables).
The windings of a three-winding transformer normally have dif-
ferent power ratings and a reference power has to be chosen,
which is used for all three windings. All the settings of the pro-
tection are then referred to the reference currents calculated
from the reference power.
250/5 A
25 MVA
1
3
2
600/5 A
20 MVA
Assuming the reference power S
currents I
and the "a" factors become:
B
S
B
=
I
B
1
´
3
U
3
TN
1
S
B
=
I
B
2
´
3
U
TN
2
S
B
=
I
B
3
´
3
U
3
TN
3
110 kV
500/5 A
5 MVA
6,3 kV
20 kV
to be 25 MVA, the reference
B
25
=
131
A
1 a
´
110
25
=
722
A
a
´
3
20
25
=
2291
A
a
´
6
3 .
ABB Switzerland Ltd
131 A
458 A
577 A
HEST 905 004b C
I
250
CT
1
=
=
=
I
131
B
1
I
600
CT
2
=
=
=
2
I
722
B
2
I
500
CT
3
=
=
=
3
I
2291
B
3
. 1
91
. 0
83
. 0
22
3-39