REG 316*4 1MRB520049-Uen / Rev. F
i
15
I
N
10
5
0
Output signal
0
Fig. 3.5.4.1 Operation of the peak value overcurrent function
Typical settings:
a) Peak value phase fault protection
I-Setting
Delay
f-min
b) Phase fault protection of a machine with synchronous starter
during start-up
I-Setting
Delay
f-min
ABB Switzerland Ltd
14.14
Setting current
10 I
N
t
t
HEST 905 028 C
according to application
0.01 s
40 Hz
1.5 I
N
5 s
2 Hz
3-69