ABB REG316 4 Series Operating Instructions Manual page 53

Numerical generator protection
Table of Contents

Advertisement

REG 316*4 1MRB520049-Uen / Rev. F
AD Config K
Defines the type of input transformer module:
0...67:
K0: transformer as specified
·
K61...K67: according to Data Sheet.
This parameter must be set before configuring the pro-
tection functions and cannot be changed subsequently.
The setting must agree with the type of input transformer
module fitted in the protection. The software does not
check the type of module fitted.
A list of input transformer modules and their codes is
included in the Data Sheet
applying the various input transformer modules are shown in
Fig. 3.1
and
Fig.
Slot Nr 1
Defines the type of I/O board in slot 1.
Not used, 316DB61, 316DB62 or 316DB63.
·
Slot Nr 2
Defines the type of I/O board in slot 2.
Not used, 316DB61, 316DB62 or 316DB63.
·
Slot Nr 3
Defines the type of I/O board in slot 3.
Not used, 316DB61, 316DB62 or 316DB63.
·
Slot Nr 4
Defines the type of I/O board in slot 4.
Not used, 316DB61, 316DB62 or 316DB63.
·
SWVers SX...
Defines the first part (letter) of the software code.
SWVers S.XXX
Defines the second part (figure) of the software code.
A list of protection functions and their software codes is included
in the Data Sheet
(see Section
(see Section
3.2.
8.).
ABB Switzerland Ltd
8.). Examples of
3-15