ABB REG316 4 Series Operating Instructions Manual page 224

Numerical generator protection
Table of Contents

Advertisement

ABB Switzerland Ltd
D. Overload function settings - OLoad-Rotor
Summary of parameters:
Text
Unit
ParSet 4..1
Trip
k1-Setting
s
I-Start
IB
t-min
s
tg
s
t-max
s
t-Reset
s
CurrentInp
AnalogAddr
IB-Setting
IN
BlockInp
BinaryAddr
Trip
SignalAddr
Start
SignalAddr
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active
Trip
defines the tripping channel activated by the tripping output of
the function (tripping logic).
k1-Setting
Multiplier. Operating characteristic constant.
I-Start
Enabling current for operating characteristic.
t-min
Minimum operating time. Operating characteristic constant.
tg
Time during which the inverse characteristic is active. Oper-
ating characteristic constant.
This must not exceed the maximum delay time.
3-186
REG 316*4 1MRB520049-Uen / Rev. F
Default
Min.
P1
(Select)
00000000
033.8
1.0
1.10
1.00
0010.0
1.0
0120.0
10.0
0300.0
100.0
0120.0
10.0
0
1.00
0.50
F
ER
ER
(see Section
5.11.).
Max.
Step
50.0
0.1
1.60
0.01
120.0
0.1
2000.0
10.0
2000.0
10.0
2000.0
10.0
2.50
0.01