ABB REG316 4 Series Operating Instructions Manual page 700

Numerical generator protection
Table of Contents

Advertisement

ABB Switzerland Ltd
Data and event numbers are needed to designate individual
items of data and events in data channels.
The table below shows the channel number mapping for a typi-
cal configuration:
Function
Current
Voltage
Delay
The function numbers in the above table correspond to the HMI
numbers.
The measured variable of the first function (current) in a device
with the slave address 2 is read as follows:
2R14V1.
The SPA bus syntax is defined in SPA BUS COMMUNICATION
PROTOCOL V2.x, 34 SPACOM EN1C.
9.5.1.
Masking events
Once all those binary inputs, IBB output signals and system and
protection function events which are not to be recorded as
events (masked) have been loaded into the device (e.g. using
W14V155), they have to be copied to the non-volatile memory
using the save command W255V255:1 so that they are not lost
should the auxiliary supply fail.
9-12
Funct. No. Chan. No. Comment
14
14
15
15
16
16
REG 316*4 1MRB520049-Uen / Rev. E
First protection function
Second protection function
Third protection function