ABB REG316 4 Series Operating Instructions Manual page 378

Numerical generator protection
Table of Contents

Advertisement

ABB Switzerland Ltd
TrigByTrip: The disturbance recorder is triggered when a
·
protection function trips (general trip). Binary signals are
not recorded.
TrigByBin1: The disturbance recorder is triggered by the
·
binary I/P 1. Binary signals are not recorded.
TrigAnyBin: Defined binary signals are recorded and re-
·
cording is triggered by any of them via an OR gate.
TrStrt&Bin: Defined binary signals are recorded and re-
·
cording is triggered by any of them via an OR gate and
also when a protection function picks up (general pick-
up).
TrTrip&Bin: Defined binary signals are recorded and re-
·
cording is triggered by any of them via an OR gate and
also when a protection function trips (general pick-up).
Note:
If the trigger conditions are connected to an OR gate and one of
them is fulfilled, the other trigger conditions bear no influence
and no further records are made. In this situation, a record is
initiated when the disturbance recorder is reset.
StorageMode
determines the procedure when the memory is full:
StopOnFull: No further data are recorded when the mem-
·
ory is full.
Overwrite: The oldest records are overwritten and there-
·
fore lost.
BinOutput
O/P signalling that recording is taking place.
MemFullSign
Warning that the memory is ¾ full. Normally, there remains
sufficient room for at least one more record after this signal is
generated.
3-340
REG 316*4 1MRB520049-Uen / Rev. F