REG 316*4 1MRB520049-Uen / Rev. F
3.5.2.
Generator differential (Diff-Gen)
A. Application
Differential protection of generators.
B. Features
non-linear current-dependent tripping characteristic
·
(see Fig. 3.5.2.1)
high stability during through-faults and c.t. saturation
·
short operating times
·
three-phase measurement
·
optimised for the differential protection of generators, i.e.
·
·
·
·
suppression of DC off-set
·
suppression of harmonics.
·
C. Inputs and outputs
I. Analogue inputs:
·
II. Binary inputs:
·
III. Binary outputs:
·
·
·
·
IV. Measurements:
·
·
·
no inrush restraint
no compensation of group of connection
only two measuring inputs
current (2 sets of 3 inputs)
blocking
tripping
R phase trip
S phase trip
T phase trip
R phase summation current
S phase summation current
T phase summation current