ABB REG316 4 Series Operating Instructions Manual page 240

Numerical generator protection
Table of Contents

Advertisement

ABB Switzerland Ltd
D. Overfluxing function settings - Overexcitat
Summary of parameters:
Text
Unit
ParSet 4..1
Trip
Delay
s
VoltageInp
CT/VT-Addr 0
V/f-Setting
UN/fN
MaxMin
BlockInp
BinaryAddr
Trip
SignalAddr
Start
SignalAddr
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active
Trip
defines the tripping channel activated by the tripping output of
the function (tripping logic).
Delay
time delay between pick-up and tripping.
VoltageInp
defines the v.t. input channel.
All voltage inputs may be selected.
V/f-Setting
Setting of the voltage/frequency ratio for tripping.
MaxMin
defines operation as overfluxing or underfluxing. Settings:
MAX:
overfluxing
MIN:
underfluxing.
3-202
REG 316*4 1MRB520049-Uen / Rev. F
Default
Min.
P1
(Select)
00000000
01.00
0.10
01.20
0.20
MAX
(Select)
F
ER
(see Section
5.11.).
Max.
Step
60.00
0.01
2.00
0.01