ABB REG316 4 Series Operating Instructions Manual page 144

Numerical generator protection
Table of Contents

Advertisement

ABB Switzerland Ltd
D. Definite time NPS function settings - NPS-DT
Summary of parameters:
Text
Unit
ParSet 4..1
Trip
Delay
s
I2-Setting
IN
CurrentInp
AnalogAddr
BlockInp
BinaryAddr
Trip
SignalAddr
Start
SignalAddr
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active
Trip
defines the tripping channel activated by the tripping output of
the function (tripping logic).
Delay
time delay between pick-up and tripping.
I2-Setting
NPS current setting for tripping.
Setting restriction:
not < 0.05 I
when supplied from protection cores.
N
CurrentInp
defines the A/D current input channel. All three-phase current
inputs may be selected. The first channel (R phase) of the
group of three selected must be specified.
BlockInp
Binary address used as blocking input.
F:
- Not blocked
T:
- Blocked
xx:
- all binary inputs (or outputs of a protection
function).
3-106
REG 316*4 1MRB520049-Uen / Rev. F
Default
Min.
P1
(Select)
00000000
01.00
0.50
00.20
0.02
0
F
ER
(see Section
5.11.).
Max.
Step
60.0
0.01
0.50
0.01