ABB REG316 4 Series Operating Instructions Manual page 258

Numerical generator protection
Table of Contents

Advertisement

ABB Switzerland Ltd
D. Overtemperature protection settings - Overtemp.
Summary of parameters:
Text
Units
ParSet 4..1
Trip
Theta-Begin
%
Theta-Warn
%
Theta-Trip
%
NrOfPhases
CurrentInp
CT/VT-Addr
IB-Setting
IN
BlockInp
BinaryAddr F
Warning
SignalAddr ER
Trip
SignalAddr ER
TimeConstant min
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active
Trip
Tripping logic (matrix) for this function.
Theta-Begin
Initial temperature rise. This temperature rise is set every
time the function is initiated, e.g. when the protection is
switched on or settings are changed.
Theta-Warn
Temperature rise at which alarm is given.
Theta-Trip
Temperature rise at which tripping takes place.
NrOfPhases
No. of phase currents measured.
CurrentInp
defines c.t. input channel.
All the current channels are available for selection. In the
case of a three-phase measurement, the first channel
(R phase) of the group of three must be selected.
3-220
REG 316*4 1MRB520049-Uen / Rev. F
Default
Min.
P1
(Select)
00000000
100
000
105
050
110
050
1
1
0
1.00
0.50
005.0
002.0
(see Section
5.11.).
Max.
Step
100
001
200
001
200
001
3
2
2.50
0.01
500.0
000.1