ABB REG316 4 Series Operating Instructions Manual page 698

Numerical generator protection
Table of Contents

Advertisement

ABB Switzerland Ltd
M29:
Write:
NAK.
Read:
returns the number of lines in a record (0...1023). A
line contains 26 Byte of data. 0 is returned if a rec-
ord has not been selected (M28).
M30:
Write:
WM30:n moves the pointer to the line to be trans-
ferred. The pointer is automatically incremented by
one every time a line is transferred until there are
no lines left. The pointer is set to 1 at the com-
mencement of data transfer (WM28:n).
Read:
RM30 returns the number of the line that was
transferred last.
M31:
Write:
NAK.
Read:
RM31 transfers the line indicated by the pointer.
V16:
Write:
WV16:1, WV16:0, deletes the oldest record.
Read:
RV16 returns the status of the disturbance re-
corder.
0: Disturbance recorder not full.
1: Disturbance recorder full.
V20:
Write:
WV20:0 terminates data transfer.
9-10
REG 316*4 1MRB520049-Uen / Rev. E