3.6.1.1.5.
Measurement inputs
Measurement inputs can be connected to the following sources:
· Measured variable constant,
integer or percent range.
· Protection function measured variable,
the range for angles is ±180.00° and currents and voltages
are transferred in the corresponding units.
· Input from the IBB,
integer range.
· C.t./v.t. input channels.
3.6.1.1.6.
Measurement outputs
Measurement outputs can be connected to the following sinks:
· Measurements Nos. 1...64.
3.6.1.1.7.
Flow chart for measurement inputs and outputs
SCS output
Fig. 3.6.1.3 Flowchart for measured variable inputs and outputs
IBB channel No. 4 is write-only and IBB channel No. 9 read-
only. The range of values for IBB channel No. 4 is -32768...
+32767 which corresponds to a 16 Bit integer.
3-298
O 1
IBB
IBB
CHAN. 4
CHAN. 9
O 64
REG 316*4 1MRB520049-Uen / Rev. F
FUPLA
function No.
V 1
Measurement
Measurement
inputs
V 64
1
outputs
SCS input
64