Entries For Double-Point Indications - ABB REB500 Communication Protocol Manual

Distributed busbar protection
Hide thumbs Also See for REB500:
Table of Contents

Advertisement

1MRK 511 451-UEN B
Read value of single entry <244>
<9> DOUBLE-POINT INFORMATION
0
0
Time stamp (CP56Time2a)
4.5.4

Entries for double-point indications

Table 25:
COD
<10> Description
<1>Current value
Table 26: Directory entry for GIN 0x46 (xx)
COD
<10> Description
<1> Current value
The following table gives an example of the ASDU 10 Generic Data that is transferred
spontaneously for a double-point indication.
Distributed busbar protection REB500
Communication protocol manual IEC60870-5-103
GEN <254>
<0>
{1, 0, 0}
43 H
01 H
Current value <1>
DATA STRUCTURE <23>
14
1,0
1
1,0
0
0
0
0
<0 .. 3>
<14>
BINARY TIME
7
1,0
Directory entry for GIN 0x4600 (header)
Data type
<1> os8ascii
<3> UI
Data type
<1> os8ascii
<23> data
structure
<9> Double
Point
INFORMATIO
N WITH
TRANSIENT
AND ERROR
<14> binary
time
© Copyright 2019 ABB. All rights reserved
Function type
Information number
Return information
identifier
Number of generic data
sets
Generic identification
number
Kind of description
DATA TYPE
DATA SIZE
NUMBER, CONT
DATA TYPE
DATA SIZE
NUMBER, CONT
DATA TYPE
DATA SIZE
NUMBER, CONT
Length
Number
Value / Significance
24
1
Double-point Indications
1
1
Number of DPI defined in this group.
Length
Number
Value / Significance
20
1
Event text defined by user
14
1
(Includes the following two
definitions)
1
1
TRANSIENT (0) /OFF (1) / ON (2) /
ERROR (3)
7
1
Time stamp (CP56Time2a)
FUN
INFORMATION
INF
OBJECT
RII
NGD {NO, COUNT, CONT}
Group <41H .. 45H>
Entry <1 .. 255>
KOD
GDD
GDD 1
GID 1
GDD 2
GID 2
GUID-F19F8A2D-F20A-4393-AEB3-66F5D3292526 v2
Section 4
IEC60870-5-103
23