ABB Switzerland Ltd
D. Balanced voltage function settings - Voltage-Bal
Summary of parameters:
Text
Unit
ParSet 4..1
Trip
V-Unbalance UN
Delay
s
t-Reset
s
NrOfPhases
s
VoltInpLine1
AnalogAddr
VoltInpLine2
AnalogAddr
BlockInp
BinaryAddr
Trip
SignalAddr
Start
SignalAddr
Trip-Line1
SignalAddr
Trip-Line2
SignalAddr
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active
Trip
defines the tripping channel activated by the tripping output of
the function (tripping logic).
V-Unbalance
Voltage difference setting for tripping.
Difference between the amplitudes of the two voltage input
channels which results in tripping. The setting applies to all
three phases in the three-phase mode.
Delay
time delay between pick-up and tripping.
t-Reset
Time required for the measurement to reset after the tripping
condition has disappeared (reset ratio: 0.90).
3-212
REG 316*4 1MRB520049-Uen / Rev. F
Default
Min.
P1
(selectable)
00000000
0.20
0.10
0.04
0.00
1.50
0.10
003
1
00000
00000
F
ER
ER
(see Section
5.11.).
Max.
Step
0.50
0.05
1.00
0.01
2.00
0.01
3
2