D. Directional overcurrent settings - DirCurrentDT
Summary of parameters:
Text
Unit
ParSet4..1
Trip
CurrentInp
CT/VT-Addr 0
VoltageInp
CT/VT-Addr 0
I-Setting
IN
Angle
Deg
Delay
s
tWait
s
MemDirMode
MemDuration
s
Receive
BinaryAddr
Ext Block
BinaryAddr
Trip
SignalAddr
Start
SignalAddr
Start R
SignalAddr
Start S
SignalAddr
Start T
SignalAddr
MeasFwd
SignalAddr
MeasBwd
SignalAddr
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active
Trip
defines the tripping channel activated by the function's
tripping output (matrix tripping logic).
CurrentInp
defines the c.t. input channel. Only three-phase c.t's can be
set and the first channel (R phase) of the group of three
selected must be specified.
VoltageInp
defines the v.t. input channel. Only three-phase v.t's can be
set and the first channel (R phase) of the group of three
selected must be specified.
3-86
REG 316*4 1MRB520049-Uen / Rev. F
Default
Min.
P1
(Select)
B00000000
2.0
0.1
45
-180
1.00
0.02
0.20
0.02
Trip
(Select)
2.00
0.20
T
F
ER
ER
ER
ER
(see Section
5.11.).
Max.
Step
20.0
0.01
+180
15
60.00
0.01
20.00
0.01
60.00
0.01