D. Rate-of-change frequency settings – df/dt
Summary of parameters:
Text
Unit
ParSet4..1
Trip
df/dt
Hz/s
Frequency
Hz
BlockVoltage
UN
Delay
s
VoltageInp
CT/VT-Addr.
Blocked (U<)
SignalAddr
BlockInp
BinaryAddr F
Trip
SignalAddr ER
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active
Trip
defines the tripping channel activated by the tripping O/P of
the function (matrix tripping logic).
df/dt
Rate-of-change of frequency pick-up setting.
Inadmissible settings:
df/dt = 0
·
df/dt > 0 for absolute frequency settings < f
·
df/dt < 0 for absolute frequency settings > f
·
3-198
REG 316*4 1MRB520049-Uen / Rev. F
Default
Min.
P1
Select
00000000
-1.0
-10.0
48.00
00.00
0.2
0.2
00.10
00.10
0
(see Section
5.11.).
Max.
Step
+10.0
0.1
65.00
0.01
0.8
0.1
60.00
0.01
N
.
N