REG 316*4 1MRB520049-Uen / Rev. F
2. Load-shedding
1st. stage
Alarm
Frequency (Hz) 49.8
Delay (s)
0.5
BlockVoltage
0.6
MaxMin
MIN
Table 3.5.18.2
2nd. stage
3rd. stage 4th. stage
Load-shed. Alarm
49.0
48.7
0.0
0.0
0.6
0.6
MIN
MIN
Typical settings for alarm and tripping stages
ABB Switzerland Ltd
5th. stage
Load-shed. Load-shed.
48.8
47.5
0.0
0.0
0.6
0.6
MIN
MIN
3-195