ABB REG316 4 Series Operating Instructions Manual page 620

Numerical generator protection
Table of Contents

Advertisement

ABB Switzerland Ltd
· spa316a.bat, lon316a.bat,
vdew316a.bat:
· spa316b.bat, lon316b.bat,
vdew316b.bat:
The type of processor board can be determined using the HMI
diagnostic function. Upon selecting 'Show diagnostic data', one
of the lines displayed is 'HW No.', which in the case of
316VC61a includes the code '0434':
HW-No.: xxxx/0434/xx
or for 316VC61b the code '04Ax':
HW-No.: xxxx/04Ax/xx
The new software is loaded into devices with the existing soft-
ware version V5.0 is accomplished by running the corresponding
batch file. For this purpose, make the active directory the HMI di-
rectory via the File Manager (Windows 3.1 or 3.11) or Explorer
(Windows 95, 98 or NT 4.0) and execute the appropriate batch
file. The version, type of processor board (316VC61a or
316VC61b) and the desired communication protocols are then
displayed again. Click on N (no) to abort or on Y (yes) to con-
tinue.
The HMI proper does not then start, but simply a window ap-
pears with the question 'Are you sure? <Y>/<N>' as a safety
precaution. If you enter 'N' the normal HMI starts; if you enter 'Y'
the settings and the program are instantly deleted. The deleting
procedure takes about twenty seconds. During this time 'Saving
restart relay' flashes on the screen.
At the end of this operation, the file '*.h26' is transferred to the
equipment. This takes about 5 minutes. During this time the pro-
gress is indicated by numbered lines and dots:
33...............................................................................................
7-22
REG 316*4 1MRB520049-Uen / Rev. C
Batch file for loading the soft-
ware into the processor unit
316VC61a, depends on com-
munications protocol.
Batch file for loading the soft-
ware into the processor unit
316VC61b, depends on com-
munications protocol.