ABB REG316 4 Series Operating Instructions Manual page 769

Numerical generator protection
Table of Contents

Advertisement

REG 316*4 1MRB520049-Uen / Rev. E
9.6.52.
Pole-Slip
Basic channel No.: 14
Summary of parameters:
Address Access Text
14S4
R
ParSet4..1
14S5
R
TRIP1
14S9
R
ZA
14S10
R
ZB
14S11
R
ZC
14S12
R
Phi
14S13
R
WarnAngle
14S14
R
TripAngle
14S15
R
n1
14S16
R
n2
14S17
R
t-Reset
Measured variables
Address
14V1
14V2
Tripping levels
Address
14Q1
14Q2
55
Unit
Default
<Select>
P1
00000000B
UN/IN
0.00
UN/IN
0.00
UN/IN
0.00
deg
090
deg
000
deg
090
01
01
s
5.000
Access
Text
Dec.
R
UN/IN
3
R
Hz
2
Access
Text
Dec.
R
UN/IN
3
R
Hz
2
ABB Switzerland Ltd
Min.
Max.
00000010B 00011110B
0.000
5.000
-5.000
0.000
0.000
5.000
60
270
0
180
0
180
0
20
0
20
0.500
25.000
Step
0.001
0.001
0.001
1
1
1
1
1
0.010
9-81

Advertisement

Table of Contents
loading