REG 316*4 1MRB520049-Uen / Rev. F
Impulse 't Puls RemTrip'
't Puls RemTrip' determines the width of the transfer tripping im-
pulse for the following signals:
Enabling and disabling the various features
A number of the function's features can be enabled and dis-
abled.
t1 active
This setting provides facility for disabling the timer t1. When it is
disabled, none of the "repeat trip" group of signals is generated.
t2 active
This setting provides facility for disabling the timer t2. When it is
disabled, none of the "backup trip" group of signals is generated.
RemTrip active
This setting provides facility for disabling transfer tripping. When
it is disabled, none of the "remote trip" group of signals is gener-
ated.
EFP active
This setting provides facility for disabling the end fault protection.
When it is disabled, none of the "end fault" group of signals is
generated.
Red active
This setting provides facility for disabling the redundant protec-
tion. When it is disabled, none of the "redundant" group of sig-
nals is generated.
Start Ext act.
This setting provides facility for disabling the unconditional trip
feature. When it is disabled, none of the "unconditional trip"
group of signals is generated.
23340 Remote Trip
23375 EFP Rem Trip.
ABB Switzerland Ltd
3-291