ABB REG316 4 Series Operating Instructions Manual page 267

Numerical generator protection
Table of Contents

Advertisement

REG 316*4 1MRB520049-Uen / Rev. F
REs":
When the input 'AdjREsInp' is enabled, the error code 123.0
is displayed initially until the resistance has been calculated.
It can take up to 10 s before the value measured for REs is
displayed.
During normal operation, the value entered for REs via the
HMC is displayed.
Normal operation: Neither of the two inputs 'AdjMTRInp' and
'AdjREsInp' is enabled and injection is taking
place.
Note:
Only one of the binary inputs may be enabled
at any one time, otherwise an error code is
generated for the measurements Rfs, MTR
and REs (see table below).
AdjMTRInp
0
1
0
1
0: binary input disabled
1: binary input enabled
AdjREsInp
0
Protection active and Rfs is
computed
0
Determination of MTR and Rfs
1
Determination of REs and Rfs
1
Error codes: MTR = 1090.0,
REs = 109.0, Rfs = 109.0
ABB Switzerland Ltd
3-229