REG 316*4 1MRB520049-Uen / Rev. F
Normal operation: Neither of the two inputs 'AdjCoupCInp' and
Note:
AdjCoupCInp
0
1
0
1
0: binary input disabled
1: binary input enabled.
'AdjRErInp' is enabled and injection is taking
place.
Only one of the binary inputs may be
enabled at any one time, otherwise an error
code is generated for the measurements Rf,
C and REr (see table below).
AdjRErInp
0
Protection active and Rf is computed
0
Determination of C and Rf
1
Determination of REr (Rf = 111.0)
1
Error codes: 109.00 and 109.00
(Rf = 109.0)
ABB Switzerland Ltd