ABB Switzerland Ltd
Utility Automation
Software (cont'd)
Technical data
Auxiliary unit for REG216/316*4 for 100%
stator and rotor earth fault protection
- Stator earth
resistance R
PS
- Stator earth
- resistance R
ES
The effective earth resistances R
the transformation ratio of the voltage trans-
former must be calculated in accordance with
the Operating Instructions.
Further details about settings of the various
functions can be obtained from the REG216/
316*4 data sheet.
Rotor earth fault protection
This function incorporates an alarm as well as
a trip level with separate tripping and signal-
ling outputs.
The function allows the measurement of the
actual coupling capacitance while the ma-
chine is standing still. This measurement per-
mits optimum settings with respect to the pro-
tected machine.
Alarm and trip levels are entered and read out
in kΩ.
Settings:
Alarm level
Delay
Trip level
Delay
R
Er
REX010 Injection unit
The injection unit REX010 is contained in a REG316*4 housing, therefore the specifications of
the design details and the general data of the REG316*4 are applicable. (Exception: Insulation
voltage for REX010: Supply = 2.8 kV DC)
Supply voltage range:
Power consumption
Optocoupler inputs:
Connection terminals:
Control and signalling devices:
green LED on:
red LED on:
yellow LED on:
ENABLE switch:
DISABLE switch:
RESET push button:
Optocoupler input:
Coupling capacitance
130 Ω to 500 Ω
Reset ratio
700 Ω to 5 kΩ
(≥4.5* R
)
PS
, R
and
kΩ)
ES
PS
Accuracy
Operating time
Machine and system parameters:
- Rotor earth
capacitance
- Rotor earth
resistance R
- Rotor earth
resistance R
- Coupling
capacitance
- Time constant
The effective earth resistances R
must be calculated in accordance with the
User's Guide.
100 Ω to 25 kΩ
Further details about settings of the various
0.2 s to 60 s
100 Ω to 25 kΩ
functions can be obtained from the REG216/
316*4 Data Sheet.
0.2 s to 60 s
900 Ω to 5 kΩ
36 to 312 V DC (refer to table below)
<150 VA
18 to 312 V DC (refer to table below)
HDFK (type Phoenix) 4 mm
Device ready
Overload
No injection
Injection on
Injection off
Reset after interruption of injection
Interruption of injection, reset after interruption of
injection
REX010/011
1MRB520123-Ben
2 µF to 10µF
110% (with
settings of <10 kΩ)
120% (with
settings of >µF10
100 Ω to 10 kΩ:
<±10%
0 to 100 Ω,
10 kΩ to 25 kΩ:
<±20%
1.5 s
200 nF to 1 µF
100 Ω to 500 Ω
Pr
900 Ω to 5 kΩ
Er
4 µF to 10 µF
T = R
x C
Er
= 3 to 10 ms
and R
Er
2
Page 4