ABB REG316 4 Series Operating Instructions Manual page 65

Numerical generator protection
Table of Contents

Advertisement

REG 316*4 1MRB520049-Uen / Rev. F
D. Transformer differential protection settings - Diff-Transf
Summary of parameters:
Text
Unit
ParSet 4..1
Trip
g
IN
v
b
IN
g-High
IN
I-Inst
IN
InrushRatio
%
InrushTime
s
a1
s1
CurrentInp1
CT/VT-Addr
a2
s2
CurrentInp2
CT/VT-Addr
a3
s3
CurrentInp3
CT/VT-Addr
BlockInp
BinaryAddr
InrushInp
BinaryAddr
HighSetInp
BinaryAddr
Trip
SignalAddr
Trip-R
SignalAddr
Trip-S
SignalAddr
Trip-T
SignalAddr
Inrush
SignalAddr
Stabilizing
SignalAddr
Explanation of Parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active
Trip
defines the tripping channel activated by the tripping output of
the function (matrix).
Default
Min.
P1
(Select)
00000000
0.2
0.1
0.50
0.25
1.50
1.25
2.00
0.50
10
3
10
6
5
0
1.00
0.05
Y
(Select)
0
1.00
0.05
y0
(Select)
0
1.00
0.05
y0
(Select)
0
F
F
F
ER
(see Section
5.11.).
ABB Switzerland Ltd
Max.
Step
0.5
0.1
0.50
0.25
5.00
0.25
2.50
0.25
15
1
20
1
90
1
2.20
0.01
2.20
0.01
2.20
0.01
3-27