ABB REG316 4 Series Operating Instructions Manual page 379

Numerical generator protection
Table of Contents

Advertisement

REG 316*4 1MRB520049-Uen / Rev. F
AnalogInp 1...AnalogInp 12
Defines the c.t. and v.t. inputs to be recorded. The setting is
the number of the I/P.
The numbers of the c.t. and v.t. inputs do not necessarily
have to agree with the numbers of the c.t. and v.t. channels,
however, no gaps are permitted (setting zero).
BinInp 1...BinInp 16
Binary inputs to be recorded (for triggering modes
"TrStrt&Bin, TrigAnyBin and TrTrip&Bin"). Binary address
(binary input or output of a protection function). No recording
takes place for F ® FALSE or T ® TRUE.
A particular order is not necessary. There may also be gaps.
BinInp 1...BinInp 16
Definition of a corresponding binary signal as one of the trig-
ger signals for initiating recording. All the trigger signals thus
defined, are connected to an OR gate so that any one of
them can start recording. Possible settings are:
No trigger: The corresponding signal has no influence on
·
the start of recording.
Trigger: A positive-going edge of the corresponding signal
·
from logical '0' to logical '1' initiates recording.
Inv. trigger: A negative-going edge of the corresponding
·
signal from logical '1' to logical '0' initiates recording.
MWAInp 1...MWAInp 12
Measured variables to be recorded.
Possible settings are:
Disconnect, no input
·
Constant measured variable, analogue value as a
·
constant
Binary output of a protection function, measured variable
·
of the selected function
Input from IBB, input variable of IBB channel 4,
·
inputs 1...64.
MWAScale1...MWAScale12
Scaling factors for reading the disturbance records.
ABB Switzerland Ltd
3-341