D. Voltage controlled overcurrent settings - Imax-Umin
Summary of parameters:
Text
Unit
ParSet 4..1
Trip
Delay
s
Current
IN
Hold-Voltage
UN
Hold-Time
s
NrOfPhases
CurrentInp
AnalogAddr 0
VoltageInp
AnalogAddr 0
BlockInp
BinaryAddr F
Trip
SignalAddr ER
Start
SignalAddr ER
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active
Trip
defines the tripping channel activated by the tripping output of
the function (tripping logic).
Delay
Time between the function picking up and tripping.
Current
Pick-up current setting.
Setting restrictions:
not > 1.6 I
when supplied from metering cores
·
N
Hold-Voltage
Voltage below which the pick-up status latches, even if the
current falls below the pick-up setting.
3-72
REG 316*4 1MRB520049-Uen / Rev. F
Default
Min.
P1
(Select)
00000000
Trip Chan
01.00
0.5
02.00
0.5
00.70
0.4
01.00
0.1
001
1
(see Section
5.11.).
Max.
Step
60.00
0.01
20
0.1
1.1
0.01
10
0.02
3
2