D. Delay/integrator function settings - Delay
Summary of parameters:
Text
Units
ParSet 4..1
Trip
Trip-Delay
s
Reset-Delay
s
Integration
0/1
BinaryInp
BinaryAddr
BlockInp
BinaryAddr
Trip
SignalAddr
Start
SignalAddr
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active
Trip
Definition of the tripping logic (matrix) excited by the
function's output.
Trip-Delay
Time between start signal at the input and the tripping signal
at the output.
Reset-Delay
Time required for the timer to reset after the input signal has
disappeared.
Integration
Determination of the response of the function in the presence
of a pulsating I/P signal:
0:
The delay continues to run, providing the I/P signal does
not disappear for longer than the reset time
3.6.3.1).
1:
The time during which the I/P is at logical "1" is inte-
grated, i.e. tripping does not take place until the sum of
logical "1" time equals the set delay time
3-306
REG 316*4 1MRB520049-Uen / Rev. F
Default
Min.
P1
(Select)
00000000
01.00
00.00
00.01
00.00
0
0
F
F
ER
ER
(see Section
5.11.).
Max.
Step
300.00
0.01
300.00
0.01
1
1
(see Fig.
(see Fig. 3.6.3.2)
.