ABB REG316 4 Series Operating Instructions Manual page 657

Numerical generator protection
Table of Contents

Advertisement

ABB Switzerland Ltd
Utility Automation
Numerical generator protection
Ancillary functions
Table 42: Logic
Logic for 4 binary inputs with the following 3 configurations:
1. OR gate
2. AND gate
3. Bistable flip-flop with 2 set and 2 reset inputs (both OR gates), resetting takes priority
All configurations have an additional blocking input.
Provision for inverting all inputs.
Table 43: Delay/integrator
· For delaying pick-up or reset or for integrating 1 binary signal
· Provision for inverting the input
Settings:
Pick-up or reset time
Integration
Table 44: Plausibility check
A plausibility check function is provided for each three-phase current and three-phase voltage input which
performs the following:
· Determination of the sum and phase sequence of the 3 phase currents or voltages
· Provision for comparison of the sum of the phase values with a corresponding current or voltage sum
applied to an input
· Function blocks for currents exceeding 2 x I
Accuracy of the pick-up setting at rated frequency
Reset ratio
Current plausibility settings:
Pick-up differential for sum of internal summation current
or between internal and external summation currents
Amplitude compensation for summation c.t.
Delay
Voltage plausibility settings:
Pick-up differential for sum of internal summation voltage
or between internal and external summation voltages
Amplitude compensation for summation v.t.
Delay
Table 45: Run-time supervision
The run-time supervision feature enables checking the opening and closing of all kinds of breakers (cir-
cuit-breakers, isolators, ground switches...). Failure of a breaker to open or close within an adjustable time
results in the creation of a corresponding signal for further processing.
Settings
Setting time
Accuracy of run time supervision
0 to 300 s in steps of 0.01 s
yes/no
respectively voltages exceeding 1.2 U
N,
±2% I
(at 0.2 to 1.2 I
N
±2% U
(at 0.2 to 1.2 U
N
>90%
>95% (at U >0.1 U
0.05 to 1.00 I
N
-2.00 to +2.00 in steps of 0.01
0.1 to 60 s in steps of 0.1 s
0.05 to 1.2 U
N
- 2.00 to +2.00 in steps of 0.01
0.1 to 60 s in steps of 0.1 s
0 to 60 s in steps of 0.01 s
±2 ms
REG316*4
1MRK502004-Ben
Page 29
N
N
N
or I >0.1 I
)
N
N
in steps of 0.05 I
N
in steps of 0.05 U
N

Advertisement

Table of Contents
loading

Table of Contents