ABB REG316 4 Series Operating Instructions Manual page 244

Numerical generator protection
Table of Contents

Advertisement

ABB Switzerland Ltd
D. Inverse time overfluxing function settings - U/f-Inv
Summary of parameters:
Text
Unit
ParSet 4..1
Trip
VoltageInp
CT/VT-Addr 0
V/f-Setting
UB/fN
VB-Setting
UN
t-min
min
t-max
min
t [V/f=1.05]
min
t [V/f=1.10]
min
t [V/f=1.15]
min
t [V/f=1.20]
min
t [V/f=1.25]
min
t [V/f=1.30]
min
t [V/f=1.35]
min
t [V/f=1.40]
min
t [V/f=1.45]
min
t [V/f=1.50]
min
t-Reset
min
BlockInp
BinaryAddr
Trip
SignalAddr
Start
SignalAddr
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active
Trip
defines the tripping channel activated by the tripping output of
the function (matrix).
VoltageInp
defines the v.t. input channel.
All voltage inputs may be selected.
3-206
REG 316*4 1MRB520049-Uen / Rev. F
Default
Min.
P1
(Select)
00000000
01.10
1.05
01.00
0.80
0.20
0.01
60.0
5.0
70.0
0.01
70.0
0.01
06.0
0.01
01.00
0.01
00.480
0.01
00.300
0.01
00.220
0.01
00.170
0.01
00.140
0.01
00.140
0.01
60.0
0.02
F
ER
(see Section
5.11.).
Max.
Step
1.20
0.01
1.20
0.01
2.00
0.01
100
0.1
100
0.01
100
0.01
100
0.01
100
0.01
30
0.001
30
0.001
30
0.001
30
0.001
30
0.001
30
0.001
100
0.1