ABB REG316 4 Series Operating Instructions Manual page 83

Numerical generator protection
Table of Contents

Advertisement

REG 316*4 1MRB520049-Uen / Rev. F
Compensation for group of connection
Phase-to-phase currents are measured in order to compare pri-
mary and secondary currents without regard to the circuit of the
transformer. The combination of these currents internally in the
protection takes account, however, of their phase relationships.
The relationships between the current vectors for different
groups of connection can be seen from the following illustrations.
For example, for a Yd5 connected transformer
I
1R
R
I
1S
S
I
1T
T
I
1R
150°
I
HEST 905 005 C
Yy0
2
1
R
R
S
S
T
T
Yd1
1
2
R
S
T
Yd7
1
2
R
R
S
S
T
T
·
Star-connected primary
I
2R
R
·
Delta-connected secondary
I
2S
S
·
Phase-angle between the currents of
I
2T
T
the same phase on both sides
5 x 30° = 150°
ì
I
ï
1r (compensated)
í
î ï
I
2r (compensated)
Yy6
I 1R
I
2R
R
S
T
Yd5
I
1R
I
2R
R
R
S
S
T
T
Yd11
I 1R
R
S
T
I
2R
ABB Switzerland Ltd
=
-
+
1 / 3 ( I
I )
1R
1S
=
I
2R
I
1
2
1R
R
S
T
I
2R
1
2
I 1R
R
S
T
1
2
I
2R
R
S
T
HEST 905 006 C
I
2R
I 1R
3-45