Numerical generator protection
Table of Contents

Advertisement

REG 316*4 1MRB520049-Uen / Rev. F
TRIP t1 L1, L2 or L3
defines the tripping channel activated by the function's trip-
ping outputs TRIP t1 L1, L2 or L3 (matrix tripping logic). This
output is activated for a phase segregated 'Retrip'.
TRIP t2
defines the tripping channel activated by the function's trip-
ping output TRIP t2 (matrix tripping logic). This output is acti-
vated for a 'Backup Trip' or 'Unconditional Trip' the after sec-
ond time step t2.
REMOTE TRIP
defines the tripping channel activated by the function's trip-
ping output REMOTE TRIP (matrix tripping logic).
RED TRIP L1, L2 or L3
defines the tripping channel activated by the function's trip-
ping outputs RED TRIP L1, L2 or L3 (matrix tripping logic).
EFP REM TRIP
defines the tripping channel activated by the function's trip-
ping output EFP REM TRIP (matrix tripping logic).
EFP BUS TRIP
defines the tripping channel activated by the function's trip-
ping output EFP BUS TRIP (matrix tripping logic).
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active
I Setting
Pick-up of the current criterion for the breaker failure protec-
tion (BFP), end fault protection (EFP) and the redundant trip-
ping logic (RED).
Delay t1
'Retrip' tripping delay
Delay t2
Backup tripping delay.
Delay tEFP
End fault protection delay.
t Drop Retrip
Reset delay for 'Retrip', 'Redundant Trip' and 'External Trip
Initiate'.
(see Section
5.11.).