Numerical generator protection
Table of Contents

Advertisement

ABB Switzerland Ltd
Utility Automation
Software
Auxiliary unit for REG216/316*4 for 100%
stator and rotor earth fault protection
The coding is achieved by alternating the
transmission of the square wave with a quies-
cent period, as seen in Fig. 3.
Fig. 3
The REG216/316*4 evaluates and compares
the measured injected voltage with the refer-
ence voltage during the transmitting period.
In the quiescent period the evaluation of pos-
sible interferences is active, ensuring the cor-
rect protection response. The injection trans-
former REX011 is equipped with a contactor,
Three protection functions are available in the
REG216/316*4 library:
- 100% Stator earth fault
protection
- Rotor earth fault protection Rotor EFP
- 95% Stator earth fault
protection
During the transmitting period, the digital fil-
ter algorithms are calculating the instanta-
neous earth fault resistance from the input
signal pairs Uis, Ui and Uir, Ui respectively.
During the quiescent period the filtered sig-
nals Uis and Uir are examined for interfer-
ence from the protected object or the connec-
ted network. This examination is used to vali-
date the previous calculation of the earth fault
resistance.
The reference signal Ui is continuously
supervised with respect to amplitude and fre-
quency. This ensures that the injection signal
is correct and that it has the correct frequency.
The primary earth connection of the protected
machine is checked through evaluation of the
capacitive component of the earth fault cur-
rent during the transmitting period.
100% Stator earth fault protection function
This function consists of an alarm level and a
trip level with corresponding signalling and
tripping outputs.
It is possible to compensate for a second
high-resistance earth to neutral point within
type P8. In the case that the earth fault current
exceeds 5 A the contactor will open the input
circuit to the injection unit to protect it
against high voltages during earth faults near
the generator terminals. The 95% function is
always active and will detect any earth faults.
The resistors R
high-resistance earthing of the generator
neutral point and for coupling the injection
signal to R
nal to R
the generator rotor where coupling is made
with the resistors R
additional capacitors C
There are three connection variants for the
stator and two for the rotor earth fault protec-
tion.
the protected zone by including the monitor-
ing of the generator circuit breaker status.
The function is capable of measuring the ef-
Stator EFP
fective value of R
ratio of the voltage transformer while the ma-
chine is at standstill. This allows optimizing
the function with the actual parameters of the
Overvoltage U>
protected machine.
Alarm and trip levels are entered and read out
in kΩ.
Settings:
Alarm level
Delay
Trip level
Delay
R
ES
Number of neutral points 2
R
-2. neutral point
ES
Reset ratio
Accuracy
Operating time
Machine and system parameters:
- Max. earth fault
current
- Stator earth
capacitance
REX010/011
1MRB520123-Ben
, R
are used to provide
ES
PS
as well as the measurement sig-
PS
. A similar arrangement applies for
ES
and R
; however, two
ER
PR
and C
are required.
1
2
and of the transformation
ES
100 Ω to 20 kΩ
0.2 s to 60s
100 Ω to 20 kΩ
0.2 s to 60 s
400 Ω to 5 kΩ
900 Ω to 30 kΩ
110% (with
settings of <10 kΩ)
120% (with
settings of >10 kΩ)
100 Ω to 10 kΩ:
<±10%
0 to 100 Ω, 10 kΩ
to 20 kΩ: <±20%
1.5 s
l
<20 A (recom-
0
mended l
0.5 µF to 6 µF
Page 3
≤5 A)
0