ABB REG316 4 Series Operating Instructions Manual page 358

Numerical generator protection
Table of Contents

Advertisement

ABB Switzerland Ltd
D. Counter settings - Count
Summary of parameters:
Text
Unit
ParSet 4..1
Trip
Count-Thresh
Drop-Time
s
Reset delay
s
BinaryInp
BinaryAddr F
BlockInp
BinaryAddr F
Trip
SignalAddr ER
Start
SignalAddr ER
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active
Trip
defines the tripping channel activated by the tripping O/P of
the function (matrix tripping logic).
Count-Thresh
Number of input impulses counted by the counter before it
trips.
Drop time
Time the counter output signal is maintained after the input
signal causing it has reset.
Reset-Delay
Time after the input signal has reset before the counter is
reset to zero if it did not trip.
BinaryInp
Counter input
xx:
- all binary inputs (or outputs of protection
functions).
3-320
REG 316*4 1MRB520049-Uen / Rev. F
Default
Min.
P1
(Select)
00000000
1
1
00.04
00.01
010.0
000.1
(see Section
5.11.).
Max.
Step
100
1
30.00
00.01
300.0
000.1