9.6.27.
OLoad-Stator
Basic channel No.: 14
Summary of parameters:
Address Access Text
14S4
R
ParSet4..1
14S5
R
TRIP
14S9
R
k1-Setting
14S10
R
I-Start
14S11
R
t-min
14S12
R
tg
14S13
R
t-max
14S14
R
t-Reset
14S15
R
IB-Setting
14S16
R
NrOfPhases
Measured variables
Address
14V1
Tripping levels
Address
14Q1
Event list
Event No.
14E1
14E2
14E3
14E4
14
Unit
Default
<Select>
P1
00000000B
s
041.4
IB
1.10
s
0010.0
s
0120.0
s
0300.0
s
0120.0
IN
1.00
3
Access
Text
Dec.
R
IN
3
Access
Text
Dec.
R
IN
3
Cause
Event mask
Trip
Set
V155
Ditto
Reset
V155
Start
Set
V155
Ditto
Reset
V155
ABB Switzerland Ltd
Min.
Max.
00000010B 00011110B
1.0
120.0
1.00
1.60
1.0
120.0
10.0
2000.0
100.0
2000.0
10.0
2000.0
0.50
2.50
1
3
Enable code
1
2
4
8
Step
0.1
0.01
0.1
10.0
10.0
10.0
0.01
2
Status
14I1
14I2
9-37