ABB REG316 4 Series Operating Instructions Manual page 310

Numerical generator protection
Table of Contents

Advertisement

ABB Switzerland Ltd
D. IDMT function settings - I0-Invers
Summary of parameters:
Text
Units
ParSet 4..1
Trip
c-Setting
k1-Setting
s
I-Start
IB
t-min.
s
NrOfPhases
CurrentInp
CT/VT-Addr
IB-Setting
I N
BlockInp
BinaryAddr
Trip
SignalAddr
Start
SignalAddr
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active
Trip
Tripping logic (matrix).
c-Setting
Setting for the exponential factor determining the shape of
the operating characteristic according to BS 142 or for se-
lecting the RXIDG characteristic.
k1-Setting
Constant determining the tripping characteristic.
I-Start
Pick-up setting (initiates the tripping characteristic).
t-min.
Definite minimum time of the tripping characteristic.
3-272
REG 316*4 1MRB520049-Uen / Rev. F
Default
Min.
P1
(Select)
00000000
1.00
(Select)
013.5
0.01
1.10
1.00
00.0
00.0
1
1
0
1.00
0.04
F
ER
ER
(see Section
5.11.).
Max.
Step
200.0
0.01
4.00
0.01
10.0
0.1
3
2
2.50
0.01