D. Inverse time overcurrent settings - Current-Inv
Summary of parameters:
Text
Unit
ParSet4..1
Trip
c-Setting
k1-Setting
s
I-Start
IB
t-min
s
NrOfPhases
CurrentInp
CT/VT-Addr 0
IB-Setting
IN
BlockInp
BinaryAddr
Trip
SignalAddr
Start
SignalAddr
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active
Trip
defines the tripping channel activated by the tripping O/P of
the function (matrix tripping logic).
c-Setting
Setting for the exponential factor determining the shape of
the operating characteristic according to BS 142 or for se-
lecting the RXIDG characteristic.
k1-Setting
Constant determining the parallel shift of the characteristic
(time grading).
I-Start
Pick-up current at which the characteristic becomes effective.
t-min
Definite minimum tripping time.
NrOfPhases
defines the number of phases measured.
3-80
REG 316*4 1MRB520049-Uen / Rev. F
Default
Min.
P1
(Select)
00000000
1.00
(Select)
013.5
0.01
1.10
1.00
00.00
0.0
1
1
1.00
0.045
F
ER
ER
(see Section
5.11.).
Max.
Step
200.0
0.01
4.00
0.01
10.0
0.1
3
2
2.50
0.01