Standstill Protection Using An Overcurrent Function - ABB REG316 4 Series Operating Instructions Manual

Numerical generator protection
Table of Contents

Advertisement

ABB Switzerland Ltd
4.2.2.2.

Standstill protection using an overcurrent function

The overcurrent function is enabled by an undervoltage function,
if the period without voltage exceeds a given time.
The standstill protection scheme comprises the following items:
an overcurrent function "Current"
an undervoltage function "Voltage"
a timer "Delay".
The block diagram can be seen from Fig. 4.4. The computing re-
quirement is 23 %.
U
I
Fig. 4.4
4-12
Function No.1 Voltage
U-Setting
= 0.85 UN
Delay
= 1.00 s
Function No.3 Current
I-Setting
Delay
Block diagram of a standstill protection scheme
based on an overcurrent function
REG 316*4 1MRB520049-Uen / Rev. B
Function No.2 Delay
Trip
TRIP time
Reset time
Block
= 1.5 IN
Trip
= 0.02 s
Standstill
protection
Trip
= 0.0 s
= 20.0 s
HEST 935 008 FL