ABB REG316 4 Series Operating Instructions Manual page 546

Numerical generator protection
Table of Contents

Advertisement

ABB Switzerland Ltd
5.12.8.
SRIO settings
Refer to 'Programming manual SRIO 1000M and 500M' having
the No. '34 SRIO 1000M 2 EN1 B' for how to program the SRIO
500/1000M.
SRIO 500/1000M must be configured as follows:
BUS_MODE:
BUS
BUS-Setup:
setup
baud
parity
stopbit
cts
dcd
aut.lf
timeout
resend
ANSI_SETUP must be set to 'half-duplex'; the other parameters
in ANSI_SETUP are of no consequence.
After the new BUS modes have been saved (STORE F), the
system has to be restarted.
The SRIO slave address must agree with the address in the file
re-01.cfg (950). The SRIO address is set in SYSPAR P4.
A (dummy) data point must be entered in the SRIO data base for
every device in the SPA-BUS loop.
5-102
Code
1
9
2
6
3
0
4
10
BUS 1
9600
2
1
1
1
1
60000
0
REG 316*4 1MRB520049-Uen / Rev. E
MODE
Saco 100M Slave mode
Fast SPA Master mode
Null mode
Terminal mode
BUS 2
BUS 4
9600
9600
2
0
1
1
0
0
0
0
0
1
3000
0
3
0