ABB REG316 4 Series Operating Instructions Manual page 658

Numerical generator protection
Table of Contents

Advertisement

ABB Switzerland Ltd
Utility Automation
Technical Data Func-
Technical Data Func-
tions (cont'd)
tions (cont'd)
Numerical generator protection
Table 46: Accuracy of the metering function UIfPQ and three-phase measuring module
(including input voltage and input current c.t.)
Input variable
Core balance c.t.s
with error compensation
Voltage
±0.5% U
Current
±0.5% I
Real power
±0.5% S
Apparent power
±0.5% S
Power factor
±0.01
Frequency
±0.1% f
×
×
Ö3
S
U
I
(three-phase)
N =
N
N
×
×
×
Ö3
S
= 1/3
U
I
(single-phase)
N
N
N
Accuracy
Protection c.t.s
without error com-
pensation
±1% U
N
N
±2% I
N
N
±3% S
N
N
±3% S
N
N
±0.03
±0.1% f
N
REG316*4
1MRK502004-Ben
Conditions
0.2 to 1.2 U
N
f = f
N
0.2 to 1.2 I
N
f = f
N
0.2 to 1.2 S
N
0.2 to 1.2 U
N
0.2 to 1.2 I
N
f = f
N
S = S
, f = f
N
N
0.9 to 1,1 f
N
N
0.8 to 1,2 U
N
Page 30