ABB REG316 4 Series Operating Instructions Manual page 204

Numerical generator protection
Table of Contents

Advertisement

ABB Switzerland Ltd
D. Power function settings - Power
Summary of parameters:
Text
Unit
ParSet 4..1
Trip
P-Setting
PN
Angle
deg
Drop-Ratio
%
Delay
s
MaxMin
Phi-Comp
deg
NrOfPhases
CurrentInp
CT/VT-Addr 0
VoltageInp
CT/VT-Addr 0
PN
UN*IN
BlockInp
BinaryAddr
Trip
SignalAddr
Start
SignalAddr
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active
Trip
channel of the tripping logic (matrix) activated by the func-
tion's tripping O/P.
P-Setting
Power setting for tripping.
Forbidden settings:
< 0.005 P
connected to metering cores
·
N
< 0.020 P
connected to protection cores
·
N
In view of the required accuracy, the use of metering cores is
recommended for settings £ 0.2 P
3-166
REG 316*4 1MRB520049-Uen / Rev. F
Default
Min.
P1
(Select)
00000000
-0.050
-0.100
000.0
-180.0
60
30
00.50
0.05
MIN
(Select)
0.0
-5.0
001
1
1.000
0.500
F
ER
(see Section
5.11.).
.
N
Max.
Step
1.200
0.005
180.0
5.0
170
1
60.00
0.01
5.0
0.1
3
1
2.500
0.001