ABB Switzerland Ltd
Diagnosis: main processor 316VC61a/316VC61b ready
·
(0001H).
Diagnosis: A/D processor EA6. not ready.
·
The external A/D processor 316EA62 or 316EA63 is not
ready. This occurs during normal operation, because the A/D
processor on the 316VC61a/316VC61b is active.
Diagnosis: internal A/D ready (0001H)
·
The A/D processor on the 316VC61a/316VC61b is ready.
Diagnosis: system status: OK.
·
The above list of diagnostic messages reflects the operating
state when the device is standing by. The following messages
and hexadecimal weightings can be generated by a fault.
Designation
Function
RDY
Device standing by
WDTO
Watchdog time-out
WDDIS
Watchdog disabled
HLT
Stop procedure initiated
SWINT
Software interrupt
RAM
RAM error
ROM
ROM error
VREF
Reference voltage out-of-tolerance
ASE
A/D converter error
EEPROM
Parameter memory error
The hexadecimal weighting of an error message may also be the
addition of simpler errors. For example, VREF and ASE are re-
corded as 0400H + 0800H = 0C00H.
Failures with a weighting less than 080H are listed as 'minor er-
rors', e.g. a warm start after pressing the reset button.
Failures with a weighting higher than 0100H are 'fatal errors' and
result in blocking of the protection and control functions.
Note: Normally, a fatal error always concerns the entire device.
An exception to this rule occurs when an EEPROM error is de-
tected on a 316EA62 or 316EA63.
6-4
REG 316*4 1MRB520049-Uen / Rev. C