REG 316*4 1MRB520049-Uen / Rev. C
Fig. 6.2
shows the diagnostic data of a device after a warm start.
The significance of the various parameters is as follows:
HW number: 000000B0A538/0434/23
·
Every 316VC61a or 316VC61b processor board has a unique
number. To this are added the codes for the microprocessor
and the PCMCIA controller (PC card).
Software
= 1998-03-17 11:38;00
·
Date and time when the device firmware was created.
Settings = 1998-03-27 11:07;47
·
Date and time when the parameter settings were last
downloaded.
A/D processor EA6. Status: not ready
·
The external 316EA62 or 316EA63 A/D processor is not fitted.
Internal A/D Status: OK
·
The A/D processor on the 316VC61a or 316VC61b is
standing by.
FUPLA status: FUPLA No. 1 (T015
·
Name of the FUPLA in the device. This uniquely identifies the
FUPLA code loaded in the device. The FUPLA code can be
processed either in the program ('Prog') or the parameter
('Para') memory. After the FUPLA code has been loaded,
processing commences in the parameter memory. It is then
copied to the program memory and runs in the background.
The processing speed of the program memory is higher.
Up to eight different FUPLA logics can be loaded at the same
time and the status of each one is displayed. The following
statuses are possible:
Blocked
The blocking input is preventing the execution of the
FUPLA logic.
Halted
The execution of the FUPLA logic has been halted
because, for example, the FUPLA code cannot be
accessed temporarily.
Processing
The FUPLA logic is being processed.
Initialised
The FUPLA logic is already initialised, but inactive.
Inactive
The FUPLA logic is loaded, but is not running.
ABB Switzerland Ltd
): Editing program
6-7