D. Current plausibility function settings - Check-I3ph
Summary of parameters:
Text
Units
ParSet 4..1
Trip
I-Setting
IN
Delay
s
CT-Compens
CurrentInp
CT/VT-Addr
SumInp.
CT/VT-Addr
BlockInp
BinaryAddr
Trip
SignalAddr
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active
Trip
Definition of the tripping logic (matrix) excited by the
function's O/P.
I-Setting
Current setting for tripping.
Delay
Time between start signal at the I/P and the tripping signal at
the O/P.
Forbidden settings:
£ 1 s for current settings £ 0.2 I
CT-Compens
Amplitude compensation factor for the residual current I/P,
enabling different transformation ratios of the main c.t's for
phase and residual currents to be equalised.
The polarity of the residual current can be reversed by enter-
ing negative values.
3-330
REG 316*4 1MRB520049-Uen / Rev. F
Default
Min.
P1
(Select)
00000000
0.20
0.05
10.0
0.1
01.00
-2.00
0
0
F
ER
(see Section
5.11.).
.
N
Max.
Step
1.00
0.05
60.0
0.1
+2.00
0.01